Soft Case Model
- 3-Pole and 2-Pole Earth Resistance
- The latest circuit design permits the instrument to operate with the minimum of influence from earth voltage and earth resistance of auxiliary earth spikes
- Dust and drip proof (designed to IEC 60529 IP54)
- Earth resistance value can be read directly from the scale
- Designed to meet IEC 61010-1 safety standard
- Capable of measuring earth voltage
- Small and lightweight. Shock-resistant new case material
- 2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test
- Lead wire connection to C and P terminals and proper auxiliary earth resistance can be checked by “OK” lamp
Lead wire connection to C and E terminals is good when “OK” lamp is illuminated
Product Overview
The Kyoritsu 4102A Earth Tester is a reliable and highly accurate instrument designed for measuring earth resistance in electrical installations. Featuring a rugged build, dustproof design, and easy-to-read analog display, it ensures stable performance in both indoor and outdoor environments. Its advanced testing mechanisms provide precise readings, making it ideal for electricians, engineers, and maintenance professionals. With simple operation and durable components, the 4102A guarantees long-term usability for safety inspections and grounding verification.
Buy 100% authentic Kyoritsu products from Kyoritsu Bangladesh—your trusted supplier for original Japan-quality test instruments.
Product Overview
Useful options for measurement
Adapter to enable use of other test leads. (MODEL 8259)

Specification
Specification
| Earth resistance measurement |
× 1ΩRange | × 10Ω | × 100Ω | |
|---|---|---|---|---|
| Measuring range | 0 to 12Ω | 0 to 120Ω | 0 to 1200Ω | |
| Accuracy | ±3% of full scale | |||
| Earth voltage measurement | ||||
| Measuring range | 0 to 30 V AC (50/60Hz) | |||
| Accuracy | ±3% of full scale | |||
| Overload protection | Earth resistance : 276V AC/DC (10 seconds) Earth voltage : 276V AC/DC (10 seconds) |
|||
| Applicable standards | IEC 61010-1 CAT Ⅲ300 V Pollution degree 2 IEC 61010-2-030, IEC 61557-1,5, IEC 60529 (IP54) |
|||
| Power source | R6(AA)(1.5V) × 6 | |||
| Dimension | 105(L) × 158(W) × 70(D) mm (including case lid) | |||
| Weight | Approx. 600g (including batteries and case lid) | |||
| Accessories | 7095A (Earth resistance test leads (Red 20m, Yellow 10m, Green 5m/1set)) 7127B (Simplified measurement probe) 8032 (Auxiliary earth spikes[2 spikes/1set]) 9121 (shoulder strap) 9084 (Carrying case) R6(AA) × 6, Instruction manual |
|||
| Optional accessories | 7245A (Precision measurement cord set) 8259 (Adapter for measurement terminal) 9164 (Carrying case [Hard]) |
|||