Kyoritsu KEW 6516BT Multi-Function Installation Tester

Key Features:

  • Color LCD 3.5″ dot matrix
  • Anti-trip technology (with 2 and 3 wire) for no trip LOOP L-PE testing on all RCDs
  • With 2 wires only, very useful in case of no neutral (i.e. three-phase motor lines)
  • High test current range of 2 Ω with 0.001 Ω resolution
  • Zs Limit compares the values required by electrical installations standard with measured results
  • Type AC, A, F, B (General and Selective), EV and Variable RCDs
  • Single and auto test, ramp test and contact voltage
  • Earth resistance test 2 and 3 wires with all accessories included
  • Resistance test 100, 250, 500, and 1000 V with auto discharge voltage
  • Continuity test at 200 mA or 15 mA with selectable buzzer for fast judgment
  • On 3-phase lines with clear indication of the sequence on the display
  • TRMS Voltage measurements 2 to 600 V, mains frequency
  • Display shows how to connect the instrument according to the function selected
  • Surge protection device test, for SPD that uses varistor
  • Portable appliance tester function, for insulation and protective conductor resistance test
  • Bluetooth – communication by “KEW CONNECT”

Kyoritsu KEW 6516BT is indeed a multi-function installation tester designed for professionals who need to test and verify the safety and functionality of electrical installations.

Specification:

Insulation resistance SPD
(Varistor)
Test voltage 100V 250V 500V 1000V Max.1000V
Measuring ranges 2.000/20.00/200.0MΩ
(Auto-ranging)
20.00/200.0/
1000MΩ
(Auto-ranging)
20.00/200.0/
2000MΩ
(Auto-ranging)
0 to 1049V
(goes up by 1V)
Accuracy ±2%rdg±6dgt
(2.000/20.00MΩ)
±5%rdg±6dgt
(200.0MΩ)
±2%rdg±6dgt
(20.00/200.0MΩ)
±5%rdg±6dgt
(1000MΩ)
±2%rdg±6dgt
(20.00/200.0MΩ)
±5%rdg±6dgt
(2000MΩ)
±5%rdg±5dgt
Rated current 1.0 to 1.2mA
@0.1MΩ
1.0 to 1.2mA
@0.25MΩ
1.0 to 1.2mA
@0.5MΩ
1.0 to 1.2mA
@1MΩ
Output short circuit current 1.5mA max
Loop impedance
Function LOOP ATT LOOP HIGH
L-PE/L-N
(3wire)
L-PE
(2wire)
L-PE
(0.01ΩRes)
L-PE
(0.001ΩRes)
High test current
(25A)
L-N/L-L
Rated voltage 100 to 260V
(50/60Hz)
48 to 260V
(50/60Hz)
48 to 260V
(50/60Hz)
100 to 260V
(50/60Hz)
48 to 500V
(50/60Hz)
Impedance range 20.00/200.0/2000Ω
(Auto-ranging)
20.00/200.0/2000Ω
(Auto-ranging)
2.000Ω 20.00Ω
Accuracy ±3%rdg±6dgt ±3%rdg±10dgt ±3%rdg±4dgt ±3%rdg±25mΩ ±3%rdg±4dgt
Nominal test current at 0Ω external
loop: Magnitude/ Duration at 230V
L-N:6A/60ms
N-PE:10mA
L-PE:15mA 20Ω:
6A/20ms
200Ω:
0.5A/20ms
2000Ω:
15mA/500ms
25A/20ms 6A/20ms
PSC/PFC
Range 2000A/20kA
(L-N(PSC)/L-PE(PFC))
2000A/20kA
(PFC)
2000A/20kA
(PFC)
2000A/50kA
(PFC)
2000A/20kA
(PSC)
Accuracy PSC/PFC accuracy is derived from measured loop impedance specification and measured voltage specification
RCD
Rated voltage 100 to 260V(50/60Hz)
Function x1/2, x1,x5,Ramp,Auto,Uc
6/10/30/100/300/500/1000mA/variable
RCD type AC(G/S) A(G/S) F(G/S) B(G/S) EV
Trip current setting x1/2,
x1,Uc
10/30/100/300/
500/1000mA(G)
10/30/100/
300/500(S)
10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300mA
6mA
(x1 only)
x5 10/30/100mA 10/30/100mA 10/30/100mA 10/30mA
Ramp 10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300/500mA
10/30/100/
300mA
6mA
Accuracy Trip
current
x1/2 -8 to -2% -10 to 0% -10 to 0% -10 to 0%
x1 +2 to +8% 0 to +10% 0 to +10% 0 to +10% 0 to +10%
x5 +2 to +8% 0 to +10% 0 to +10% 0 to +10%
Ramp -4 to +4% -10 to +10% -10 to +10% -10 to +10% -10 to +10%
Trip
time
x1/2 2000ms(G/S):±1%rdg±2ms
x1 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms 10.5s:±1%±2㎳
x5 410ms(G/S):±1%rdg±2ms
Continuity
Range 20.00/200.0/2000Ω (Auto-ranging)
Open circuit voltage(DC) 7 to 14V
Measuring
current
200mA 200mA or more(2Ω or less)
15mA 15mA±3mA(short-circuit)
Accuracy ±2%rdg±8dgt
Volts
Range 300.0/600V(Auto-ranging)
Measuring
ranges
Volts 2 to 600V
Frequency 45 to 65Hz
Accuracy Volts ±2%rdg±4dgt
Frequency ±0.5%rdg±2dgt
Phase Rotation
Rated voltage 48 to 600V(45 to 65Hz)
Remarks Remarks Correct phase sequence: are displayed “1.2.3” and mark
Reversed phase sequence: are displayed “3.2.1” and mark
Earth
Range 20.00/200.0/2000Ω(Auto-ranging)
Accuracy ±2%rdg±0.08Ω(20.00Ω)
±2%rdg±3dgt(200.0/2000Ω)
General
Applicable standards IEC 61010-1 CAT IV 300V / CAT III 600 V Pollution degree 2
IEC 61010-2-034, IEC 61557-1,2,3,4,5,6,7,10
IEC 60529(IP40), IEC 61326(EMC)
Communication interface USB, Bluetooth® 5.0
Power source LR6 (AA) (1.5V) ×8
Communication interface USB
Dimension / Weight 136(L) × 235(W) × 114(D) mm / 1350g (including batteries)