Kyoritsu KEW 6011A Multi-Function Installation Tester is designed to comply with IEC 61557, offering advanced functionality for testing continuity, insulation, loop impedance.
Specification
Continuity Testing | ||
---|---|---|
Measuring Ranges | 20/200/2000Ω (Auto-ranging) | |
Open Circuit Voltage | >6V | |
Short Circuit Current | >200mA DC | |
Accuracy | ±(1.5%rdg+3dgt) | |
Insulation Testing | ||
Measuring Ranges | 20/200MΩ (Auto-ranging) | |
Test Voltage | 250V 500V 1000V DC | |
Output Voltage on Open Circuit | 250V+40 to 0% 500V+30 to 0% 1000V+20 to 0% |
|
Rated Current | > 1mA | |
Accuracy | ±(1.5%rdg+3dgt) | |
Loop Impedance Testing | ||
Rated Voltage | 230V AC +10 to 15% [50Hz] | |
Voltage Measuring Range | 100 to 250V AC [50Hz] | |
Impedance Ranges | 20/200/2000Ω | |
Nominal Test Current | 25A (20Ω range) 15mA (200Ω range) 15mA (2000Ω range) | |
Accuracy | 20Ω range ±(3%rdg +4dgt) 200Ω range ±(3%rdg +8dgt) 2000Ω range ±(3%rdg +4dgt) |
|
PSC Testing | ||
Rated Voltage | 230V AC +10 to 15% [50Hz] | |
PSC Ranges | 200A (15mA Test Current) 2000A (25A Test Current) 20kA (25A Test Current) |
|
Accuracy | PSC accuracy derived from measured loop impedance specification and measured voltage specification |
|
RCD Testing | ||
Rated Voltage | 230V AC +10 to 15% [50Hz] | |
Trip Current Settings | RCD × 1/2 : 10,30,100,300,500,1000mA RCD × 1 : 10,30,100,300,500,1000mA RCD × 5 : 10,30,100,300mA (on × 5 ranges max current 1A) |
|
Trip Current Duration | RCD × 1/2 × 1: 2000ms RCD fast: 50ms |
|
Accuracy | Trip current +10 to 0% of test current at 230V Trip time ±(1%rdg + 3dgt) |
|
Applicable standards | IEC 61010-1 CAT Ⅲ 300V Pollution Degree 2, IEC 61010-2-034, IEC 61557 | |
Power source | R6/LR6 × 8 | |
Dimension | 130(L) × 183(W) × 100(D)mm | |
Weight | Approx. 1100g | |
Accessories | KAPM10 (Test lead with IEC connecter)*1 7122B (Test leads) 7132A (External earth probe) 8923 (Fuse[0.5A/600V]) × 1 (included), 1 (spare) 9092(Cord case) 9121 (Shoulder Strap) R6(AA) × 8 Instruction Manual |
|