Kyoritsu KEW 2062 Clamp Power Meter

Key Features:

  1. AC Current Measurement: It can measure AC current up to 2000 A with high precision.
  2. Power (W, VA, VAR) Measurement: Measures active power (W), apparent power (VA), and reactive power (VAR), which is useful for monitoring and optimizing electrical systems.
  3. Voltage Measurement: It can measure AC voltage up to 600 V, offering a wide range for different electrical systems.
  4. Frequency Measurement: The meter can measure the frequency of the AC system, helping in the detection of power quality issues.
  5. True RMS Measurement: Ensures accurate readings for non-sinusoidal waveforms, a common characteristic of modern electrical systems.
  6. Data Hold Function: Allows users to freeze the current reading on the display for easy recording or further analysis.
  7. Large LCD Display: Features a large, backlit LCD display for easy viewing of measurements, even in low-light environments.
  8. Harmonics Detection: Capable of measuring and analyzing harmonics, important for assessing power quality and efficiency.
  9. Peak Hold: Captures the peak value of the measurement for dynamic or transient signals.

Applications:

  • Electrical testing and maintenance
  • Power consumption analysis
  • Power quality monitoring
  • Troubleshooting electrical systems
  • Industrial and commercial electrical inspections

The KEW 2062 is known for its durability and ease of use, making it a trusted tool for professionals looking to ensure optimal performance and safety of electrical systems.

Category:

Kyoritsu KEW 2062 Clamp Power Meter

The Kyoritsu KEW 2062 Clamp Power Meter is a versatile and compact measuring instrument designed to accurately assess electrical parameters in AC systems. This device is ideal for professionals working in electrical maintenance, diagnostics, and troubleshooting.

Specification

Wiring connections 1P2W, 1P3W, 3P3W, 3P4W
Measurements and
parameters
Voltage, Current, Frequency, Active power, Reactive power, Apparent power, Power factor(cosθ), Phase angle, Harmonics(THD-R/THD-F), Phase rotation
ACV
Range 1000V
Accuracy ±0.7%rdg±3dgt (40.0 to 70.0Hz)
±0.3%rdg±5dgt (70.1Hz to 1KHz)
Crest factor 1.7 or less
ACA
Range 40.00/400.0/1000A (3 range auto)
Accuracy ±1.0%rdg±3dgt (40.0 to 70.0Hz)
±2.0%rdg±5dgt (70.1Hz to 1kHz)
Crest factor 3 or less on 40.00A/400.0A range, 3 or less 1500A peak on 1000A range
Frequency
Display Range 40.0 to 999.9Hz
Accuracy ±0.3%rdg±3dgt
Active power
Range 40.00/400.0/1000kW
Accuracy ±1.7%rdg±5dgt (PF1, sine wave, 45 to 65Hz)
Apparent power
Range 40.00/400.0/1000kVA
Accuracy ±1dgt against each calculated value
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Reactive power
Range 40.00/400.0/1000kVar
Accuracy ±1dgt against each calculated value
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Power factor
Display Range -1.000 to 0.000 to +1.000
Accuracy ±1dgt against each calculated value
Sum: add errors of each channel, 3P3W: ±2dgt, 3P4W:±3dgt
Phase angle (1P2W only)
Display Range -180.0 to 0.0 to +179.9
Accuracy Within ±3.0°
Harmonics RMS(Content rate)
Analysis order 1st to 30th order
Accuracy ±5.0%rdg ± 10dgt (1 to 10th)
±10%rdg ± 10dgt (11 to 20th)
±20%rdg ± 10dgt (21 to 30th)
Total harmonics THD-R/THD-F
Display Range 0.0% to 100.0%
Accuracy ±1dgt against the calculated results of each measured value
Phase rotation ACV 80 to 1100V (45 to 65Hz)
Other functions MAX/MIN/AVG/PEAK, Data hold, Bluetooth®, Backlight, Auto power off
General
Power source LR6 (AA) (1.5V) ×2
Continuous
measuring time
Approx. 58 hours
Conductor size φ55 mm max. (busbar of 80mm × 30mm)
Dimension / Weight 247(L) × 105(W) × 50(D) mm / Approx. 490g (including batteries)
Applicable standards IEC 61010-1, IEC 61010-2-032, IEC 61326-1,2-2 ClassB
CAT Ⅳ 300V / CAT Ⅲ 600V / CAT Ⅱ 1000V Pollution degree 2
Accessories 7290 (Voltage test lead set)
9198 (Carrying case)
LR6(AA)×2, Instruction Manual