Kyoritsu 6516BT Multi Function Installation Tester
The KYORITSU KEW 6516BT-EV2 is a multi-function installation tester tailored for EV (Electric Vehicle) charging station installations and testing. Equipped with Bluetooth connectivity, it allows for convenient data transfer and remote monitoring. This versatile tester performs essential tests such as insulation resistance, loop impedance, continuity, and RCD testing, ensuring EV station installations meet safety and performance standards. Compact and efficient, the KEW 6516BT-EV2 is a valuable tool for professionals in EV infrastructure and electrical safety compliance.
Are you trying to find a good, Insulation Tester? Yes, this is the perfect moment and place for you. Kyoritsu Bangladesh is offering testing supplies and tools in Bangladesh. As a result, You could be able to purchase the desired tool from us in Bangladesh with the most affordable price and delivery options.
Specification
Insulation resistance | SPD (Varistor) |
||||||
---|---|---|---|---|---|---|---|
Test voltage | 100V | 250V | 500V | 1000V | Max.1000V | ||
Measuring ranges | 2.000/20.00/200.0MΩ (Auto-ranging) |
20.00/200.0/ 1000MΩ (Auto-ranging) |
20.00/200.0/ 2000MΩ (Auto-ranging) |
0 to 1049V (goes up by 1V) |
|||
Accuracy | ±2%rdg±6dgt (2.000/20.00MΩ) ±5%rdg±6dgt (200.0MΩ) |
±2%rdg±6dgt (20.00/200.0MΩ) ±5%rdg±6dgt (1000MΩ) |
±2%rdg±6dgt (20.00/200.0MΩ) ±5%rdg±6dgt (2000MΩ) |
±5%rdg±5dgt | |||
Rated current | 1.0 to 1.2mA @0.1MΩ |
1.0 to 1.2mA @0.25MΩ |
1.0 to 1.2mA @0.5MΩ |
1.0 to 1.2mA @1MΩ |
‐ | ||
Output short circuit current | 1.5mA max | ‐ | |||||
Loop impedance | |||||||
Function | LOOP ATT | LOOP HIGH | |||||
L-PE/L-N (3wire) |
L-PE (2wire) |
L-PE (0.01ΩRes) |
L-PE (0.001ΩRes) High test current (25A) |
L-N/L-L | |||
Rated voltage | 100 to 260V (50/60Hz) |
48 to 260V (50/60Hz) |
48 to 260V (50/60Hz) |
100 to 260V (50/60Hz) |
48 to 500V (50/60Hz) |
||
Impedance range | 20.00/200.0/2000Ω (Auto-ranging) |
20.00/200.0/2000Ω (Auto-ranging) |
2.000Ω | 20.00Ω | |||
Accuracy | ±3%rdg±6dgt | ±3%rdg±10dgt | ±3%rdg±4dgt | ±3%rdg±25mΩ | ±3%rdg±4dgt | ||
Nominal test current at 0Ω external loop: Magnitude/ Duration at 230V |
L-N:6A/60ms N-PE:10mA |
L-PE:15mA | 20Ω: 6A/20ms 200Ω: 0.5A/20ms 2000Ω: 15mA/500ms |
25A/20ms | 6A/20ms | ||
PSC/PFC | |||||||
Range | 2000A/20kA (L-N(PSC)/L-PE(PFC)) |
2000A/20kA (PFC) |
2000A/20kA (PFC) |
2000A/50kA (PFC) |
2000A/20kA (PSC) |
||
Accuracy | PSC/PFC accuracy is derived from measured loop impedance specification and measured voltage specification | ||||||
RCD | |||||||
Rated voltage | 100 to 260V(50/60Hz) | ||||||
Function | x1/2, x1,x5,Ramp,Auto,Uc | ||||||
6/10/30/100/300/500/1000mA/variable | |||||||
RCD type | AC(G/S) | A(G/S) | F(G/S) | B(G/S) | EV | ||
Trip current setting | x1/2, x1,Uc |
10/30/100/300/ 500/1000mA(G) 10/30/100/ 300/500(S) |
10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300mA |
6mA (x1 only) |
|
x5 | 10/30/100mA | 10/30/100mA | 10/30/100mA | 10/30mA | – | ||
Ramp | 10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300/500mA |
10/30/100/ 300mA |
6mA | ||
Accuracy | Trip current |
x1/2 | -8 to -2% | -10 to 0% | -10 to 0% | -10 to 0% | – |
x1 | +2 to +8% | 0 to +10% | 0 to +10% | 0 to +10% | 0 to +10% | ||
x5 | +2 to +8% | 0 to +10% | 0 to +10% | 0 to +10% | – | ||
Ramp | -4 to +4% | -10 to +10% | -10 to +10% | -10 to +10% | -10 to +10% | ||
Trip time |
x1/2 | 2000ms(G/S):±1%rdg±2ms | – | ||||
x1 | 550ms(G):±1%rdg±2ms,1000ms(S):±1%rdg±2ms | 10.5s:±1%±2㎳ | |||||
x5 | 410ms(G/S):±1%rdg±2ms | – | |||||
Continuity | |||||||
Range | 20.00/200.0/2000Ω (Auto-ranging) | ||||||
Open circuit voltage(DC) | 7 to 14V | ||||||
Measuring current |
200mA | 200mA or more(2Ω or less) | |||||
15mA | 15mA±3mA(short-circuit) | ||||||
Accuracy | ±2%rdg±8dgt | ||||||
Volts | |||||||
Range | 300.0/600V(Auto-ranging) | ||||||
Measuring ranges |
Volts | 2 to 600V | |||||
Frequency | 45 to 65Hz | ||||||
Accuracy | Volts | ±2%rdg±4dgt | |||||
Frequency | ±0.5%rdg±2dgt | ||||||
Phase Rotation | |||||||
Rated voltage | 48 to 600V(45 to 65Hz) | ||||||
Remarks | Remarks Correct phase sequence: are displayed “1.2.3” and mark Reversed phase sequence: are displayed “3.2.1” and mark |
||||||
Earth | |||||||
Range | 20.00/200.0/2000Ω(Auto-ranging) | ||||||
Accuracy | ±2%rdg±0.08Ω(20.00Ω) ±2%rdg±3dgt(200.0/2000Ω) |
||||||
General | |||||||
Applicable standards | IEC 61010-1 CAT IV 300V / CAT III 600 V Pollution degree 2 IEC 61010-2-034, IEC 61557-1,2,3,4,5,6,7,10 IEC 60529(IP40), IEC 61326(EMC) |
||||||
Communication interface | USB, Bluetooth® 5.0 | ||||||
Power source | LR6 (AA) (1.5V) ×8 | ||||||
Communication interface | USB | ||||||
Dimension / Weight | 136(L) × 235(W) × 114(D) mm / 1350g (including batteries) | ||||||
Accessories | Mains test lead*1 7281 (Test leads with remote control switch) 7246 (Distribution board test lead) 7228A (Earth resistance test leads) 8041 (Auxiliary earth spikes[2 spikes/1 set]) 9084 (Soft case) 9142 (Carrying case) 9151 (Shoulder strap) 9199 (Shoulder pad) LR6(AA) × 8 Instruction manual Calibration certificate |
||||||
Optional Accessories | 8212-USB (USB adapter) 8259 (Adapter for measurement terminal) 7272 (Precision measurement cord set) 8017A (Extension prod long) 8602 (EVSE ADAPETER) |