Kyoritsu 4200 Earth Clamp Tester

The earth resistance from 0.05 to 1500Ω can be measured without the auxiliary earth spikes in multi-earthing systems

Key Features:

  • The earth resistance from 0.05 to 1500Ω can be measured without the auxiliary earth spikes in multi-earthing systems
  • True RMS leakage or phase current readings from 0.1mA to 30.0A provides vital additional information in earthing networks
  • Filter function offers increased immunity to electrical noise and a Noise mark appears in excessively high noisy environments
  • Memory function up to 100 data

Note: A single earthing can not be measured. (Only for Multiple Earthing System)

Category:

Kyoritsu 4200 Earth Clamp Tester:

The Kyoritsu 4200 Earth Clamp Tester is a reliable and efficient device for measuring earth resistance and leakage current without disconnecting the grounding system. Its clamp design ensures quick, non-invasive testing, making it ideal for live systems. With high accuracy, a compact build, and easy operation, it’s perfect for professionals handling grounding inspections in industrial and commercial environments.

 

Specification

Earth resistance (Auto-ranging) 20.00/200.0/1500Ω
±1.5%±0.05Ω(0.00 to 20.99Ω)*1
±2%±0.5Ω(16.0 to 99.9Ω)
±3%±2Ω(100.0 to 209.9Ω)
±5%±5Ω(160 to 399Ω)
±10%±10Ω(400 to 599Ω)
Values are displayed, but accuracy isn’t guaranted(600 to 1580Ω)
AC current (50/60Hz)
(Auto-ranging)
100.0/1000mA/10.00/30.0A
±2%±0.7mA(0.0 to 104.9mA)
±2%(80mA to 31.5A)
Operating indication Earth resistance function :
Constant voltage injection
Current detection (Frequency : Approx.2400Hz)
Dual Integration
AC current function : Successive approximation
Over-range indication “OL”is displayed when input exceeds the upper limit of a measuring range
Response time Approx. 7 seconds (Earth resistance)
Approx. 2 seconds (AC current)
Sample rate Approx. 1 times per second
Current consumption Approx. 50mA (max.100mA)
Measurement time Approx.12 hours (when R6 is used)
Approx.24 hours (when LR6 is used)
Auto power off Turns power off about 10 minutes after the last button operation.
Conductor size Approx. Ø32mm
Applicable standards IEC 61010-1 CAT Ⅳ 300V Pollution degree2
IEC 61010-2-032, IEC 61326 (EMC)
Power source LR6/R6 (AA)(1.5V) x 4
Dimension 246(L)×120(W)×54(D)mm
Weight Approx. 780g (including batteries)
Accessories 8304 (Resister for operation check)
9166 (Carrying case[Hard])
R6 x 4, Instruction manual

Reviews

There are no reviews yet.

Be the first to review “Kyoritsu 4200 Earth Clamp Tester”