Kyoritsu 8148 leakage and load current clamp sensor. To monitor energy saving and to control the electric facilities, it is essential and imperative to control the leak and load currents from mains and branch power lines up to the equipment. The clamp sensor is easy to carry and simple to install. Rated current 100A AC. 68mm conductor size. Output voltage: AC 5000mV/100A (AC 50mV/A). Output connector: Mini-DIN 6-pin. 0 to 50 degree c temperature range. Withstand voltage: 3540V AC for 5 seconds. Approximate 2m cable length. Approximate 60 ohm output impedance.
Specification
Conductor size | Ø68mm |
---|---|
Rated current | AC 100A |
Output voltage | AC 5000mV/100A (AC 50mV/A) |
Accuracy | 0 to 80A ±1.0%rdg±0.1mV (50/60Hz) ±2.0%rdg±0.2mV (40Hz to 1kHz) 80 to 100A ±5.0%rdg (50/60Hz) ±10.0%rdg (45Hz to 1kHz) |
Cable length | Approx. 2m |
Output connector | MINI DIN 6PIN |
Output impedance | Approx. 60Ω |
Applicable standards | IEC 61010-1 , IEC 61010-2-032 CAT III 300V pollution degree 2 , IEC 61326 |
Operating temperature and humidity range | 0 to 50°C , relative humidity 85% or less (no condensation) |
Dimension | 186(L) x 129(W) x 53(D) mm |
Weight | Approx.510g |
Accessories | 9094 (Carrying case) Instruction manual , Cable marker |
Optional Accessories | 7146 (Banana Ø4 adjuster plug) 7185 (Extension Cable) |